CHECK AND TEST 1
Check reworking record.
Check to see if compressor running ratio is 100%.
DIAGNOSIS 1
Discharge refrigerant: Cut off the charging tube with pliers.
Discharge all refrigerant toward the exhaust vent.
CHECK AND TEST 2
Test brazed joints in compressor niche for leakage with soapy water.
DIAGNOSIS 2
PROCEDURE 2
Clean paint from brazed joint.
Cut off brazed joint with leakage.
Use a larger copper tube to connect 2 ends of brazed joint.
Follow below link to find out right brazing materials, Click below link to get more details for brazing requirements, go to Annex B1
Inject nitrogen at 1.57Mpa through quick connector into pipe and use soapy water to perform leakage test again.
DIAGNOSIS 3
CHECK AND TEST 3
Charge nitrogen of 1.57Mpa through quick connector into pipe.
Do leakage test on brazing points and piezometer.
DIAGNOSIS 4
CHECK AND TEST 3
Give the system 1.57Mpa Nitrogen, and then observe if there is rust and/or spotted holes on pipes of compressor niche and evaporator.
If it seems like there is a hole there, apply soapy water to the rusty area to check.
DIAGNOSIS 5
PROCEDURE 3
Clean paint off brazed joint of drying-filter.
Cut off drying-filter.
Cut off capillary and shake to remove the cut end.
DIAGNOSIS 6